Precautions
Precautions for Power Cable Installation
1. Cables must be loaded and unloaded using a crane or forklift; horizontal transport or placement is prohibited to prevent external damage or abrasion caused by manual dragging. During the installation of large cables, a cable‑laying carriage must be used to avoid improper handling and rough construction practices.
2. All installation sites shall be free of standing water to prevent moisture from entering the cables during installation and operation, which could impair their normal use.
3. Prior to installation, cable terminations must be sealed and protected to prevent water ingress and exposure to other corrosive substances, which could cause discoloration and rusting of the steel and copper tapes, as well as oxidation of the conductor and aging of the insulation layer, leading to dielectric breakdown.
4. When cables are installed parallel to heating pipelines, a clearance of 2 m shall be maintained; when crossing, a clearance of 0.5 m shall be maintained. When cables are installed parallel to or cross other pipelines, a clearance of 0.5 m shall be maintained. For directly buried cable installations, the burial depth for 1–35 kV cables shall be no less than 0.7 m.
5. When 10 kV and lower cables are installed in parallel, the clear distance between them shall be no less than 0.1 m; for 10–35 kV cables, the clearance shall be no less than 0.25 m. At crossings, the clearance shall be no less than 0.5 m.
6. The cable laying temperature shall not be lower than 0°C, and the cable bending radius must be greater than or equal to 20 times the cable diameter.
7. Cable joints rated 6 kV and above
(1) When installing cable terminations, the semi-conductive shield must be removed. Care must be taken during this process not to damage the insulation; avoid knife marks and uneven surfaces, and smooth them with sandpaper if necessary. The end of the shield should be even, and any graphite layer (particles) must be thoroughly cleaned off.
(2) The copper tape shield and armor of plastic-insulated cable terminations must be properly grounded to prevent induced voltages at the armor ends during unbalanced three-phase operation, which could lead to arcing and sheath burning. The grounding lead shall be made of tinned braided copper wire; when connecting it to the cable’s copper tape, use soldering with a soldering iron rather than flame‑soldering to avoid damaging the insulation.
(3) The three-phase copper tape shield shall be connected to ground separately; note that the shield grounding conductor and the armor grounding conductor shall be routed separately, insulated from each other, and the grounding point should be located as low as possible.
8. Basic requirements for cable terminations and splices: a) Good conductor connection; b) Reliable insulation; c) Effective sealing; d) Sufficient mechanical strength to withstand various operating conditions.
9. If cables cannot be laid promptly for any reason, they should be stored in a dry location to prevent exposure to the elements, which could cause water ingress at the cable terminations, leading to short circuits, conductor oxidation, and corrosion of other materials, thereby affecting the cable’s service life.
Note: Electrical wire and cable installation should be performed by installers or dedicated technicians who are familiar with the performance of wires and cables. If any issues remain unclear, please consult the relevant technical department or our company’s Technical Department.