Methods for Addressing Damage to the Outer Sheath of High-Voltage Cables

2022-12-26

Author:

Minglei Cable


When a high-voltage cable is damaged, it should be repaired only after confirming that there is no internal damage. Otherwise, repairing the cable jacket will have little practical benefit. The cable should be repaired promptly; otherwise, over time, the ingress of external water and moisture will compromise its service life.

When a high-voltage cable is damaged, it should be repaired only after confirming that there is no internal damage. Otherwise, repairing the cable jacket will have little practical benefit. The cable should be repaired promptly; otherwise, over time, the ingress of external water and moisture will compromise its normal service life.

Methods for Addressing Damage to the Outer Sheath of High-Voltage Cables

When the insulation layer of a high-voltage cable is damaged and the damage depth exceeds 10% of the insulation thickness, insulation reinforcement shall be performed. During insulation repair, first clean any contaminants from the damaged area, then repair it using self-adhesive insulating tape. Take care to protect against dust and water during wrapping.

When wrapping self‑adhesive insulating tape, the overlap pressure between adjacent turns of high‑voltage cable insulation tape shall be half the tape width. The repair thickness shall exceed the depth of the insulation damage and shall be no less than two layers; in areas with severe damage, at least five layers are required. The repair length at each end of the damaged section shall be 20 mm. Alternatively, a dedicated insulating shielding sleeve may be used to cover the damaged portion of the conductor’s insulation, with the open ends sealed by wrapping with insulating adhesive tape.

Within the same span, no more than three repair locations shall be made on the insulation layer of a single high-voltage cable conductor. When removing the conductor’s insulation and semiconductor layers, use dedicated tools to avoid damaging the conductor. The insulation and conductor at the cut edges shall be chamfered at 45°. All contact ends, joints, and cut edges of insulated conductors must be properly insulated and protected to prevent exposure of any wire or joint and to guard against water ingress.

Damage to cables during the laying process is unpredictable. To reduce associated costs and resolve issues promptly, a key factor is ensuring adequate staffing during cable installation; routine laying should employ proper cable‑laying equipment to prevent and minimize sheath damage. During the operation of high‑voltage cables, maintenance and inspections along the cable route must be strengthened.

All necessary tools and materials for on-site cable repair have been prepared. Sealing materials such as high-voltage cable insulation tape, waterproof tape, and stripped outer jackets from plastic insulation and sheathing are also ready, since cable insulation and sheathing materials are primarily classified into cross-linked polyethylene, polyethylene, and polyvinyl chloride.


Online Feedback

Fill out the form with your details, and our team will assist you in finding the best solution.

Submit Now

Related posts


In-depth Analysis of the Working Principle of Aluminum Alloy Cables: A Practical Technical Guide for Selecting Safe Wiring Solutions in Industrial and Civil Applications by 2026

This paper focuses on the core operating principles of aluminum alloy cables, dissecting their technical underpinnings across four dimensions: conductor modification, current-carrying and transmission, structural protection, and thermal stability and conduction. Drawing on publicly available test data from China’s cable industry in 2026, it outlines applicable scenarios and common selection pitfalls, offering practical technical guidance for wiring projects in the construction, industrial, and new energy sectors. Throughout, the presentation remains objective, avoiding exaggerated claims.