Inspection and Test Report-4


Inspection and Test Report-4
Serial number Major category Test Items Unit Technical Requirements Test Results Single-item judgment
4 Insulation Mechanical Properties Tensile strength of finished cable sections after additional aging (100±2℃, 168h) N/mm² — 20.4, 21.3, 20.2 —
Insulation Mechanical Properties Rate of change in tensile strength before and after additional aging of finished cable sections % Maximum ±25 -9, -3, -11 Qualified
Insulation Mechanical Properties Elongation at break of finished cable sections after additional aging (100±2°C, 168 h) — — 450, 410, 420 —
Insulation Mechanical Properties Rate of change in elongation at break before and after additional aging of finished cable sections % Maximum ±25 -4, -9, -7 Qualified
Insulation Mechanical Properties Hot Extension Test (200±3℃, 15 min, 20 N/cm²) — Maximum Elongation Under Load % Up to 175 45, 50, 48 Qualified
Insulation Mechanical Properties Hot elongation test (200±3℃, 15 min, 20 N/cm²) — Maximum permanent elongation after cooling % Up to 15 0, 0, 0 Qualified
Insulation Mechanical Properties Shrinkage Test (130±3℃, 1h) — Shrinkage Rate % Up to 4 1, 1, 1 Qualified
Insulation Mechanical Properties Insulation Water Absorption Test (85±2℃, 336h) — Weight Gain mg/cm² Maximum 1 0.4, 0.4, 0.4 Qualified
Insulation Mechanical Properties Peelability Test of Pre-Aging Shielding — Peel Force N Maximum 45 32‑39, 33‑37, 33‑39 Qualified
Minimum 4
Insulation Mechanical Properties Peelability test of the shield after aging (100±2℃, 7×24h) — Peel force N Maximum 45 28‑35, 30‑36, 30‑35 Qualified
Minimum 4
Insulation Mechanical Properties Insulation Surface Inspection — After the peel test conducted before and after aging, the insulation surface shall show no damage or traces of residual semiconductive shielding. √, √, √ Qualified
5 Mechanical Properties of the Sheath Tensile strength before aging (stretching speed: 250 mm/min) N/mm² Minimum 12.5 17.9 Qualified
Mechanical Properties of the Sheath Elongation at break before aging % Minimum 150 225 Qualified
Mechanical Properties of the Sheath Tensile strength after air oven aging (100±2℃, 168h) N/mm² Minimum 12.5 17.5 Qualified
Mechanical Properties of the Sheath Rate of change in tensile strength before and after air oven aging % Maximum ±25 -2 Qualified
Mechanical Properties of the Sheath Elongation at break after air oven aging (100±2℃, 168h) % Minimum 150 200 Qualified
Mechanical Properties of the Sheath Rate of change in elongation at break before and after air oven aging % Maximum ±25 -11 Qualified
Mechanical Properties of the Sheath Tensile strength of finished cable sections after additional aging (100±2℃, 168h) N/mm² — 17 —