What measures are used to prevent or reduce electrical interference in control cables?
The main measures for controlling cables to prevent or reduce electrical interference include the following three aspects:
1. Ground one spare conductor of the control cable.
Practice has shown that grounding the spare cores in control cables can reduce the amplitude of interference voltage to 25%–50%, with only a modest increase in cable cost and simple implementation.
2. Control cables shall not be used in circuits that may cause severe electrical interference.
This utility model comprises: (1) a low-current signal control circuit and a high-current signal control circuit; (2) low-level and high-level signal circuits; (3) under no circumstances shall the same control cable be used at each stage of the AC circuit breaker’s opening process.
3. Metallic Shielding and Shielding Layer Grounding
Metallic shielding is an important measure for mitigating and preventing electrical interference, encompassing full shielding, sub‑shielding, and double full shielding. The selection of metallic‑shielded control cables should be based on the cable’s immunity to interference and its electrical potential, including comprehensive measures to reduce interference, in order to meet requirements for both interference reduction and voltage levels. High interference‑immunity requirements entail significant investment. When steel‑tape armor and wire braid provide complete shielding, the cable price decreases by 10%–20%.
For control interference in high-current circuits, where the signals are strong, non‑metallic shielded control cables may be used unless the circuit is located within an extra‑high‑voltage switchgear or runs close to and parallel with high‑voltage cables. When control cables serving low‑level signal circuits are installed in environments subject to interference and no effective anti‑interference measures are available, metallic‑shielded control cables should be selected to prevent electrical interference from causing maloperation or insulation breakdown in low‑level signal circuits.
The principles for selecting the shielding type of control cables in the signal circuits of computer monitoring systems are as follows:
(1) Digital signals can be masked;
(2) For high-level analog signals, overall shielding of the conductor cores shall be used; if necessary, individual shielding of the conductor cores may also be employed.
(3) For low-level analog or pulse signals, use secondary shielding for the conductor cores; if necessary, a composite overall shield with secondary shielding for the conductor cores may also be used.
The following points should be observed regarding the grounding of the shielding layer:
(1) The shielding of control cables in the analog signal circuits of computer-based temporary control systems shall be grounded at a single point. This is because ensuring the normal operation of the computer monitoring system requires it; even an interference voltage of only about 1 V can cause errors in logical decision-making. Centralized grounding helps prevent ground loops.
(2) Except that the shielding of control cables in computer monitoring systems shall be grounded at only one point, the shielding of other control cables shall be grounded at two points when electromagnetic induction interference is significant, and at one point when electrostatic induction interference is significant.
(3) The inner shield of double-shielded or composite full-shielded cables shall be grounded at a single point, while the outer shield may be grounded at two points.
(4) When selecting a two-point grounding scheme, it should also be ensured that the shielding layer will not burn out under transient current conditions.